Post Insulators

Application

Indoor post insulators of cast resin can be used for all indoor plants , also in the tropics. They are suitable for temperatures from -25 °C to +90 °C.

Construction

Indoor post insulators of cast resin are cyclindrical solid insulators. The main dimensions and mechanical requirements are innaccordance with , IEC 60273 -1990.

Test

The following tests to IEC 60660 -1999 are performed :
Type test ,

  • Test with rated power -frequency withstand voltage (dry).
  • Test with rated lightning impulse withstand voltage .
  • Testing of minumum failing loads (nominal loads) for ;
    • Bending , tension ,torsion

Rutin Testler

  • Visual inspection.
  • Dimensional inspection.
  • Testing of conductive connection of threaded fixing bushes.
  • Partial discharge extinction voltage test.

Technical Details

TYPE kg. kV N Rippes L t D d1 d2 d3 e1 e2 e3 e4
JO4 - 60 10S 500 0.43 7.2 5000 3 95 36 60 M12 M12 M6 15 30 15 14
JO4 - 75 10N 500 0.60 12 5000 5 130 36 62 M16 M12 M6 24 36 15 14
JO8 - 75 10N 1000 1.00 12 10000 5 130 46 80 M20 M16 M10 27 42 33 15
JO16 - 75 10N 1600 1.35 12 1600 4 130 64 91 M20 M16 M10 42 68 30 17
JO4 - 95 15N 500 1 17.5 5000 6 175 36 70 M16 M12 M6 33 45 15 14
JO8 - 95 15N 1000 1.52 17.5 10000 6 175 46 85 M20 M16 M10 27 46 33 15
JO4 - 125 20N 500 1.25 24 5000 8 175 36 74 M16 M12 M6 33 50 15 14
JO8 - 125 20N 1000 1.95 24 10000 8 210 46 86 M20 M16 M10 27 44 33 15
JO4 - 170 30N 500 1.86 36 5000 11 300 36 76 M16 M12 M6 33 54 15 14
JO10 - 170 30N 1000 3.42 36 10000 11 300 46 99 M24 M16 M10 36 60 33 15
JO13 - 170 30N 1250 4.54 36 12500 11 300 46 115 M24 M16 M10 36 78 33 15